Calculate wire voltage drop based on wire gauge (AWG), length, current, and material. NEC recommends keeping voltage drop below 3%.
| Property | Value |
|---|---|
| Wire gauge | AWG 10 |
| Resistance (Copper) | 0.9989 Ω/1000ft |
| Round-trip resistance | 0.1998 Ω |
| Voltage drop | 2.997 V |
| % Voltage drop | 2.5% |
| End voltage | 117 V |
| AWG | Copper | Aluminum | Area (cmil) |
|---|---|---|---|
| 4/0 | 0.04901 | 0.0805 | 211,600 |
| 3/0 | 0.0618 | 0.1015 | 167,800 |
| 2/0 | 0.07793 | 0.128 | 133,100 |
| 1/0 | 0.09827 | 0.1615 | 105,600 |
| 1 | 0.1239 | 0.2036 | 83,690 |
| 2 | 0.1563 | 0.2567 | 66,360 |
| 3 | 0.197 | 0.3237 | 52,620 |
| 4 | 0.2485 | 0.4082 | 41,740 |
| 6 | 0.3951 | 0.6491 | 26,250 |
| 8 | 0.6282 | 1.032 | 16,510 |
| 10 | 0.9989 | 1.641 | 10,380 |
| 12 | 1.588 | 2.608 | 6,530 |
| 14 | 2.525 | 4.148 | 4,107 |
| 16 | 4.016 | 6.595 | 2,583 |
| 18 | 6.385 | 10.49 | 1,624 |
| 20 | 10.15 | 16.68 | 1,022 |
Calculate voltage drop across a wire run with our free calculator, important for electrical installations to ensure devices receive adequate voltage.
Voltage Drop = Current × Resistance, where wire resistance depends on wire gauge, length, and material (typically copper or aluminum). Longer wire runs and thinner gauges (higher resistance) produce greater voltage drop.
Common electrical guidelines suggest keeping voltage drop under 3-5% for most circuits, though specific requirements vary by application and local electrical codes.
Thinner wires (higher gauge number) have higher resistance per unit length, causing more voltage drop for the same current and distance compared to thicker wires.
Voltage drop calculations typically account for the complete circuit (out and back), so round-trip distance matters, check your specific calculator's convention.
Excessive voltage drop can cause devices to underperform, motors to run hot, or lights to dim, especially noticeable at the far end of long wire runs.